Warning – Heat & Glo Fireplace RED40ST User Manual
Page 24
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
24
Figure 7.4
Top Vent - Horizontal Termination
Venting with 1 elbow
H
1
V
1
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
Note: Use DVP Series
components only.
V
1
Minimum
H
1
Maximum
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
6 ft.
1829
3 ft.
914 mm
9 ft.
2743
4 ft.
1219 mm
12 ft.
3658
5 ft.
1524 mm
15 ft.
4572
6 ft.
1829 mm
18 ft.
5486
7 ft.
2134 mm
21 ft.
6401
8 ft.
2438 mm
24 ft.
7315
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
Note: 12 inches minimum vertical is
required prior to attaching any elbow
to the appliance.