Vent information and diagrams, A. approved pipe, C. use of elbows – Heat & Glo Fireplace RED40ST User Manual
Page 23: B. vent table key, D. measuring standards, E. vent diagrams
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P
• 10/12
23
A. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies DVP venting systems. Refer to Section
16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect (see
Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows
(see Figure 7.1).
Figure 7.1
7
7
Vent Information and Diagrams
B. Vent Table Key
The abbreviations listed in this vent table key are used in
the vent diagrams.
D. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.
• Pipe measurements are shown using the effective length
of pipe (see Figure 7.2).
• Measurements are made from the appliance outer wrap,
not from the standoffs.
• Horizontal terminations are measured to the outside
mounting surface (fl ange of termination cap).
• Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with no rise.
Symbol
Description
V
1
First section (closest to appliance) of vertical length
V
2
Second section of vertical length
H
1
First section (closest to appliance) of horizontal length
H
2
Subsequent sections of horizontal length
Horizontal
Vertical
8-1/2 in.
8-
1
/2
i
n
.
12
in
.
A
B
1-1/4 in. (32 mm)
OVERLAP
Figure 7.2 Chimney Offset/Return
E. Vent Diagrams
General Rules:
• When penetrating a combustible wall, a wall shield
fi restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop
must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
Effective
Height/
Length
Figure 7.3 Pipe Effective Length
Pipe
Effective Length
Inches
Millimeters
DVP4
4
102
DVP6
6
152
DVP12
12
305
DVP24
24
610
DVP36
36
914
DVP48
48
1219
DVP6A
3 to 6
76 to 152
DVP12A
3 to 12
76 to 305
DVP12MI
3 to 12
76 to 305
DVP24MI
3 to 24
76 to 610