Warning, Top vent - horizontal termination - (continued), Two elbows – Hearth and Home Technologies DV3732SBIL User Manual

Page 25

background image

25

Hearth & Home Technologies • DV3732SBI, DV3732SBIL • 2215-900 Rev. G • 2/13

INSTALLED

HORIZONTALLY

H

1

H

2

V

1

1. Top Vent - Horizontal Termination - (continued)

Note: There MUST be a 25% re-
duction in total H when using fl ex
vent except when using the sim-
ple up and out installation (see
Figure 7.3).

Figure 7.5

Two Elbows

V

1

Minimum**

H

1

+ H

2

Maximum

90 Elbow Only**

1/2 ft.

152 mm

1/2 ft.**

152 mm

1 ft.

305 mm

1-1/2 ft.**

457 mm

2 ft.

610 mm

2-1/2 ft.**

762 mm

4 ft.

1.2 m

3-1/2 ft.

1.1 m

6 ft.

1.8 m

4-1/2 ft.

1.4 m

14 ft.

4.3 m

H

1

+ H

2

MAX. =14 ft. (4.3 m)

V

1

+ H

1

+ H

2

MAX. = 40 ft. (12.2 m)

**See Warning Below.

Fire Risk.

• When using SLP-HRC-SS and SLP-HRC-ZC-SS

termination caps on top vented fi replaces, a one
foot minimum vertical vent section is required
before installing fi rst elbow.

• When using DVP-TB1 termination cap on top

vented fi replaces, a three foot minimum vertical
vent section is required before installing fi rst
elbow.

WARNING**

Note: Use SLP Series
components only.