beautypg.com

A.5 configuring smart meter using pushbuttons – Honeywell ST 3000 User Manual

Page 78

background image

A.5

Configuring Smart Meter Using Pushbuttons,

Continued

Setting Upper Display
Values

The procedure in Table A-8 outlines the steps for setting the upper
display limit to represent the 100 percent (URV) output of the
transmitter.

ATTENTION

This procedure applies only for Flow units (GPM or GPH) in a
transmitter configured for SQUARE ROOT output conformity, or
CUSTOM unit in a transmitter configured for linear or square root
output conformity.

Table A-8

Setting Upper Display Value for Smart Meter Display

Step Action

Meter

Display

1

Press UPPER VALUE button to initiate upper

display limit setting function.

If upper limit display value was previously set,

KNOWN VALUE indicator lights and set value

flashes in display.

2

Press UPPER VALUE button again within 5

seconds. Otherwise, meter exits limit setting

function.

Display shows magnitude range selection.

%

100

0

ANALOG

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

19 .99

ATTENTION

The magnitude range

selection only applies for setting the display
limits. This selection does not affect the
normal operation of the meter. During normal
operation, the display is automatically ranged
to provide the best precision possible.

Continued on next page

68

ST 3000 Release 300 Installation Guide

2/05