A.5

Configuring Smart Meter Using Pushbuttons,

Continued

Selecting Engineering
Units

The procedure in Table A-5 outlines the steps for selecting the desired
engineering units for a smart meter using its local adjustments on the
face of the meter. You will be selecting the unit of measurement that
you want the smart meter to indicate during normal operation.

WARNING

When the transmitter’s end-cap is removed, the housing is not
explosionproof.

Table A-5

Selecting Engineering Units

Step Action

Meter

Display

1

Loosen lock on meter end-cap and unscrew

cap from housing. Be sure transmitter power

is ON.

2

Press UNITS SET button.

Display shows code for current engineering

units setting.

%

100

0

EU

ANALOG

%

0

UPPER

VALUE

UNITS

LOWER

VALUE

S E T

VAR

SEL.

3

Press Increase key to call up next code or

Decrease key to call up previous code.

Repeat this action until desired code is on

display.

You can hold down the Increase or Decrease

key to scroll forward or backward through the

codes.

ATTENTION

Remember that if transmitter

is configured for SQUARE ROOT output

conformity the only valid code selections are

EU0 (%)

EUD (GPM)

EUE (GPH)

EUF (Custom)

If transmitter is configured for LINEAR output

conformity EU0 (%) to EUC and EUF

(CUSTOM) are valid code selections.

Selection codes for engineering units

%

100

0

EU

ANALOG

1

UPPE R

VALUE

UNITS

LOWER

VALUE

S E T

VA R

SEL.

In H O

2

EU0 = %*
EU1 = inH

2

O*

EU2 = mmHg*
EU3 = PSI*
EU4 = KPa
EU5 = MPa
EU6 = mbar
EU7 = bar
EU8 = g/cm

2

EU9 = Kg/cm

2

EUA = mmH

2

O

EUB = inHg
EUC = mH

2

O

EUD = GPM*
EUE = GPH*
EUF = Custom

Press and hold to
scroll forward
through selections

Press and hold to
scroll backward
through selections

*These selections
have indicators on
the display.

Continued on next page

2/05

ST 3000 Release 300 Installation Guide