beautypg.com

Honeywell ST 3000 User Manual

Page 53

background image

4.3

Wiring ST 3000 Transmitter,

Continued

Conduit seal

Transmitters installed as explosionproof in a Class I, Division 1, Group
A Hazardous (Classified) Location in accordance with ANSI/NFPA 70,
the US National Electrical Code (NEC), require a “LISTED”
explosionproof seal to be installed in the conduit, within 18 inches of
the transmitter. Crouse-Hinds

®

type EYS/EYD or EYSX/EYDX are

examples of “LISTED” explosionproof seals that meets this
requirement.

Transmitters installed as explosionproof in a Class I, Division 1, Group
B, C or D Hazardous (Classified) Locations do not require an
explosionproof seal to be installed in the conduit.

NOTE: Installation should conform to all national and local electrical
code requirements.

WARNING

When installed as explosionproof in a Division 1 Hazardous Location,
keep covers tight while the transmitter is energized. Disconnect power
to the transmitter in the non-hazardous area prior to removing end caps
for service.

When installed as nonincendive equipment in a Division 2 Hazardous
Location, disconnect power to the transmitter in the non-hazardous area,
or determine that the location is non-hazardous prior to disconnecting or
connecting the transmitter wires.

Continued on next page

2/05

ST 3000 Release 300 Installation Guide

43