B–38, Appendix b – Hitachi SJ200 Series User Manual
Page 252
![background image](/manuals/88658/252/background.png)
ModBus Data Listing
Appendix B
B–38
C082
OI input span calibra-
tion
R/W Scale factor between the
external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%
00C8h
0 to 2000
0.1 %
C085
Thermistor input tuning
R/W Range is 0.0 to 200.0%
00EEh
0 to 2000
0.1 %
C086
[AM] terminal offset
tuning
R/W Range is 0.0 to 10.0V
00C9h
0 to 100
0.1 V
C091
Debug mode enable
—
Displays debug parameters.
Two option codes:
00... Disable
01... Enable
—
—
—
C101
Up/Down memory
mode
selection
R/W Controls speed setpoint for the
inverter after power cycle. Two
option codes:
00... Clear last frequency
(return to default frequency
F001)
01... Keep last frequency
adjusted by UP/DWN
00CFh
0, 1
—
C102
Reset selection
R/W Determines response to Reset
input [RST].
Three option codes:
00... Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01... Cancel trip state at signal
OFF transition, stops inverter if
in Run Mode
02... Cancel trip state at input
signal ON transition, no effect
if in Run Mode
00D0h
0, 1, 2
—
C141
Input A select for logic
output
R/W
See
00EFh
0, 1, 2, 3,
4, 5, 6, 7,
8, 9
—
C142
Input B select for logic
output
R/W
00F0h
C143
Logic function select
R/W Applies a logic function to
calculate [LOG] output state,
three options:
00... [LOG] = A AND B
01... [LOG] = A OR B
02... [LOG] = A XOR B
00F1h
0, 1, 2
—
C144
Terminal [11] ON delay R/W Range is 0.0 to 100.0 sec.
00F2h
0 to 1000
0.1 sec
C145
Terminal [11] OFF
delay
R/W Range is 0.0 to 100.0 sec.
00F3h
0 to 1000
0.1 sec
“C” Group Intelligent Terminal Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.