Forward run/stop and reverse run/stop commands – Hitachi SJ200 Series User Manual
Page 139
Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–12
Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run
command via the terminal [RV], the inverter executes the Reverse Run command (high)
or Stop command (low).
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single
Run key issues a Run FWD command or Run REV command. However, it has no effect
on the [FW] and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the
motor starts rotation and is dangerous! Before turning power ON, confirm that the Run
command is not active.
Option
Code
Terminal
Symbol
Function Name
State
Description
00
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
Valid for inputs:
C001, C002, C003, C004,
C005, C006
Required settings:
A002 = 01
Notes:
•
When the Forward Run and Reverse Run
commands are active at the same time, the inverter
enters the Stop Mode.
•
When a terminal associated with either [FW] or
[RV] function is configured for normally closed,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
Example (default input configuration shown—
see page
1
2
3
4
5
6
L
PCS
See I/O specs on page
FW
RV