beautypg.com

B–12, Appendix b – Hitachi SJ200 Series User Manual

Page 226

background image

Network Protocol Reference

Appendix B

B–12

The data set in the response is as follows:

When the Read Coil Status command cannot be executed normally, refer to the
exception response.

Write in Coil [05h]:

This function writes data in a single coil. Coil status changes are as follows:

An example follows (note that to command the inverter, set A002=03):

• Sending a RUN command to an inverter having slave address “10”

• This example writes in coil number “1.”

Response Buffer

4

5

6

7

8

9

Coil Number

+ 0 (high

order)

+ 0 (low

order)

+ 1 (high

order)

+ 1 (low

order)

+ 2 (high

order)

+ 2 (low

order)

Coil Status

00h

07h

00h

09h

00h

FFh

Trip data

Over-voltage trip

Under-voltage trip

No trip

Data

Coil Status

OFF to ON

ON to OFF

Change data (high order)

FFh

00h

Change data (low order)

00h

00h

Query:

Note 1:

No response is made for a
broadcasting query.

Response:

No.

Field Name

Example

(Hex)

1

Slave address *1

0A

2

Function code

05

3

Coil start number
(high order)

00

4

Coil start number
(low order)

01

5

Change data
(high order)

FF

6

Change data
(low order)

00

7

CRC-16 (high order)

DC

8

CRC-16 (low order)

81

No.

Field Name

Example

(Hex)

1

Slave address

0A

2

Function code

05

3

Coil start number
(high order)

00

4

Coil start number
(low order)

01

5

Change data
(high order)

FF

6

Change data
(low order)

00

7

CRC-16 (high order)

DC

8

CRC-16 (low order)

81