beautypg.com

Output terminal configuration – Hitachi SJ200 Series User Manual

Page 118

background image

“C” Group: Intelligent Terminal Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–46

Output Terminal Configuration

The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.

The output logic convention is programmable for terminals [11], [12], and the alarm
relay terminals. The open-collector output terminals [11] and [12] default to normally
open (active low), but you can select normally closed (active high) for these terminals in
order to invert the sense of the logic. You can invert the logical sense of the alarm relay
output as well.

“C” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

C021 Terminal [11] function

10 programmable functions

available for logic (discrete)

outputs (see next section)

01

[FA1]

01

[FA1]

OUT-TM 11 FA1

C022 Terminal [12] function

00

[RUN]

00

[RUN]

OUT-TM 12 RUN

C026 Alarm relay terminal

function

05

[AL]

05

[AL]

OUT-TM RY AL

C028 [AM] signal selection

Two available functions:
00... Actual motor speed
01... Motor current
(see after next section)

00

output

freq.

00

output

freq.

AM-KIND F

“C” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

C031 Terminal [11] active

state

Select logic convention, two
option codes:
00... normally open (NO)
01... normally closed (NC)

00

00

O/C-11 NO

C032 Terminal [12] active

state

Select logic convention, two
option codes:
00... normally open (NO)
01... normally closed (NC)

00

00

O/C-12 NO

C036 Alarm relay active state Select logic convention, two

option codes:
00... normally open (NO)
01... normally closed (NC)

01

01

O/C-RY NC