Hitachi SJ200 Series User Manual
Page 116
“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–44
13
USP
Unattended Start
Protection
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
15
SFT
Software Lock
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
16
AT
Analog Input
Voltage/current
Select
ON
Terminal [OI] is enabled for current input (uses
terminal [L] for power supply return)
OFF
Terminal [O] is enabled for voltage input (uses
terminal [L] for power supply return)
18
RS
Reset Inverter
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
19
PTC
PTC Thermistor
Thermal Protection
ANLG
When a thermistor is connected to terminals [6]
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
OPEN
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
20
STA
Start
(3-wire interface)
ON
Starts the motor rotation
OFF
No change to present motor status
21
STP
Stop
(3-wire interface)
ON
Stops the motor rotation
OFF
No change to present motor status
22
F/R
FWD, REV
(3-wire interface)
ON
Selects the direction of motor rotation: ON =
FWD. While the motor is rotating, a change of
F/R will start a deceleration, followed by a
change in direction.
OFF
Selects the direction of motor rotation: OFF =
REV. While the motor is rotating, a change of F/
R will start a deceleration, followed by a change
in direction.
23
PID
PID Disable
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=01).
OFF
Has no effect on PID loop operation, which
operates normally if PID Enable is active
(A071=01).
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description