ModBus Data Listing
Appendix B
B–30
A094
Select method to switch
to Acc2/Dec2 profile
R/W Two options for switching
from 1st to 2nd accel/decel:
00... 2CH input from terminal
01... transition frequency
007Ch
0, 1
—
A294
Select method to switch
to Acc2/Dec2 profile,
2nd motor
R/W
007Dh
A095
Acc1 to Acc2 frequency
transition point
R/W Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 400.0 Hz
007Eh
0 to 4000
0.1 Hz
A295
Acc1 to Acc2 frequency
transition point, 2nd
motor
R/W
007Fh
A096
Dec1 to Dec2 frequency
transition point
R/W Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
0080h
0 to 4000
0.1 Hz
A296
Dec1 to Dec2 frequency
transition point, 2nd
motor
R/W
0081h
A097
Acceleration curve
selection
R/W Set the characteristic curve of
Acc1 and Acc2, two options:
00... linear
01... S-curve
0082h
0, 1
—
A098
Deceleration curve
selection
R/W Set the characteristic curve of
Acc1 and Acc2, two options:
00... linear
01... S-curve
0083h
0, 1
—
A101
[OI]–[L] input active
range start frequency
R/W The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz
0084h
0 to 4000
0.1 Hz
A102
[OI]–[L] input active
range end frequency
R/W The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz
0085h
0 to 4000
0.1 Hz
A103
[OI]–[L] input active
range start current
R/W The starting point for the
current input range.
Range is 0. to 100.%
0086h
0 to 100
1 %
A104
[OI]–[L] input active
range end current
R/W The ending point for the
current input range.
Range is 0. to 100.%
0087h
0 to 100
1 %
A105
[OI]–[L] input start
frequency enable
R/W Two options:
00... Use A101 start value
01... Use 0Hz
0088h
0, 1
—
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.