The following table lists the holding registers for the “A” Group Standard Functions.
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.
A001
Frequency source
setting
R/W Five options; select codes:
00... Keypad potentiometer
01... Control terminal
02... Function F001 setting
03... ModBus network input
10... Calculate function output
002Dh
0 to 3, 10
—
A002
Run command source
setting
R/W Three options; select codes:
01... Control terminal
02... Run key on keypad, or
digital operator
03... ModBus network input
002Eh
1, 2, 3
—
A003
Base frequency setting
R/W Settable from 30 Hz to the
maximum frequency
002Fh
30 to
max. freq.
1 Hz
A203
Base frequency setting,
2nd motor
R/W Settable from 30 Hz to the 2nd
maximum frequency
0030h
30 to
max. freq.
2
1 Hz
A004
Maximum frequency
setting
R/W Settable from the base
frequency up to 400 Hz
0031h
30 to 400
1 Hz
A204
Maximum frequency
setting, 2nd motor
R/W Settable from the 2nd base
frequency up to 400 Hz
0032h
30 to 400
1 Hz
A005
[AT] selection
R/W Four options, select codes:
00... Select between [O] and
[OI] at [AT]
01... [O] + [OI] ([AT] input is
ignored)
02... Select between [O] and
keypad potentiometer
03... Select between [OI] and
keypad potentiometer
0033h
0, 1, 2, 3
—
A011
Pot./O–L input active
range start frequency
R/W The output frequency corre-
sponding to the analog input
range starting point,
range is 0.0 to 400.0
0034h
0 to 4000
0.1 Hz
A012
Pot./O–L input active
range end frequency
R/W The output frequency corre-
sponding to the analog input
range ending point,
range is 0.0 to 400.0
0035h
0 to 4000
0.1 Hz
A013
Pot./O–L input active
range start voltage
R/W The starting point (offset) for
the active analog input range,
range is 0. to 100
0036h
0 to 100
1 %
A014
Pot./O–L input active
range end voltage
R/W The ending point (offset) for
the active analog input range,
range is 0. to 100.
0037h
0 to 100
1 %