Using Intelligent Input Terminals

Oper

ations

and Monitor

ing

4–18

Two-stage Acceleration and Deceleration

When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and F003) to use the second set of accelera-
tion/deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002 acceleration time 1, and F003 decelera-
tion time 1). Use A092 (acceleration time 2)
and A0093 (deceleration time 2) to set the
second stage acceleration and deceleration
times.

In the graph shown above, the [2CH] becomes active during the initial acceleration. This
causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).

Output

frequency

[FW],

[RV]

[2CH]

t

target

frequency

second

initial

1
0

1
0

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

09

2CH

Two-stage Accelera-
tion and Deceleration

ON

Frequency output uses 2nd-stage acceleration
and deceleration values

OFF

Frequency output uses the initial acceleration 1
and deceleration 1 values

Valid for inputs:

C001, C002, C003, C004,
C005, C006

Required settings:

A092, A093, A094=00

Notes:

Function A094 selects the method for second stage
acceleration. It must be set = 00 to select the input
terminal method in order for the [2CH] terminal
assignment to operate.

1

2

3

4

5

6

L

PCS

Example (default input configurations
shown—see page

3–41

):

See I/O specs on page

4–6

.

–FU and FR

models

–FE

models

2CH