B–37, Appendix b – Hitachi SJ200 Series User Manual
Page 251

SJ200 Inverter
Appendix B
B–37
C041
Overload level setting
R/W Sets the overload signal level
between 0% and 200% (from 0
to two times the rated current
of the inverter)
00BBh
0 to
20000
0.01 %
C042
Frequency arrival
setting for acceleration
R/W Sets the frequency arrival
setting threshold for the output
frequency during acceleration,
range is 0.0 to 400.0 Hz
00BCh
0 to 4000
*1
0.1 Hz
C043
Arrival frequency
setting for deceleration
R/W Sets the frequency arrival
setting threshold for the output
frequency during deceleration,
range is 0.0 to 400.0 Hz
00BDh
0 to 4000
0.1 Hz
C044
PID deviation level
setting
R/W Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%
00BEh
0 to 1000
0.1 %
C052
PID FBV function high
limit
R/W When the PV exceeds this
value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%
00EAh
0 to 1000
0.1 %
C053
PID FBV function low
limit
R/W When the PV goes below this
value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%
00EBh
0 to 1000
0.1 %
C071
Communication speed
selection
—
NOTE: These network settings
are not accessible to ModBus.
Use the inverter keypad or
digital operator to edit. Refer to
00C0h
—
—
C072
Node allocation
—
00C1h
—
—
C074
Communication parity
selection
—
00C3h
—
—
C075
Communication stop bit
selection
—
00C4h
—
—
C076
Communication error
select
—
00ECh
—
—
C077
Communication error
time-out
—
00EDh
—
—
C078
Communication wait
time
—
00C5h
—
—
C081
O input span calibration
R/W Scale factor between the
external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%
00C7h
0 to 2000
0.1 %
“C” Group Intelligent Terminal Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.