Analog value comparator/threshold comparator:
A1 – A16
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command:
Read
89
–
Write
8D
–
Response:
Read successful
–
C2
Write successful
–
C1
Command
rejected
–
C0
1
2
Type
8D
8D
3
Instance
2
00 – 0F
00 – 0F
4
Index
Table 24
5 – 8
Data 1 – 4
depending on index J Table 25
1) Possible causes J page 91
2) EZ provides 16 analog comparators A1 to A16 for use as
required. These can be addressed using the instance (0 – F).