Set cycle time function block ST01
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 94
J
page 94
1
Command:
Read
92
–
Write
B2
–
Response:
Read successful
–
C2
Write successful
–
C1
Command
rejected
–
C0
2
Type
2C
2C
3
Instance
01
01
4
Index
J
Table 110
J
Table 110
5 – 8
Data 1 – 4
Read operation
00
depending on
index,
J
Table 111
Write operation
depending on
index,
J
Table 111
00