Control commands for EZ700
MN05013001E
54
Local inputs: I1 – I16
This command string enables you to read the local inputs of
the EZ700 basic unit. The relevant input word is stored in Intel
format.
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command: Read
88
–
Response:
Read successful
–
C2
Command
rejected
–
C0
1)
2
Len
02
02
3
Type
84
84
4
Index
00
00
5
Data 1 (Low Byte)
00
J
Table 13
6
Data 2 (High Byte)
00
J
Table 13
7 – 8
Data 3 – 4
00
00
1) Possible causes J page 91