6
Control commands for EZ700
Data exchange procedure
The “Control commands 9 bytes” module allows extended
data exchange of the EZ700 on the PROFIBUS-DP
communication bus. This allows you to transfer services from
the following areas:
• Read/write image date and time (Page 45)
• Read/write image data (Page 49) and
• Read/write function block data (Page 72).
A data exchange procedure is required in order to ensure the
safe exchange of data via PROFIBUS-DP from master to
slave and vice versa.
Requirement:
The “Control commands 9 byte” module must have been
selected.
Attention!
While a control command is being executed, the input and
output data will remain in the state before the control
command was called. Only after the “Control commands”
data exchange has been completed, will the I/O data be
refreshed.
Caution!
Only those values specified for the command code should
be used.
Check the values that you write in order to avoid
malfunctions.