Control commands for EZ700
MN05013001E
58
Markers: M1 – M16/N1 – N16
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command: Write
8C
–
Response:
Write successful
–
C1
Command
rejected
–
C0
1
2
Len
01
01
3
Type
2
With M marker
86
86
With N marker
87
87
4
Index
2
00 – 0F
00 – 0F
5
Data 1 (Low Byte)
3
00/01
00/01
6 – 8
Data 2 – 4
00
00
1) Possible causes J page 91
2) There are 16 M markers and 16 N markers. The markers are
addressed by Type and Index:
Use Type to select the M or N marker.
Use Index to select the marker number.
3) The marker is set if a value is written to the data byte that does
not equal zero. The marker is reset accordingly if the value 0
is written to data byte Data 1.