background image

4.6 Controller Settings

4-13

4

3. Registering the controller.

The selected logical port defines the parameters displayed in the section circled in the
above dialog box. Click the

Add

Button to add it to the

Current Assignments

List on the

right. When all the controllers have been registered, click the

Close

Button to close the

dialog box.

The

Logical Port

Pull-down List lists only ports that were assigned to a driver in

4.5.1

Communication Setting Dialog Box

.

a)

Controller Setting

Dialog Box for Memobus

Specify the CPU serial address (Machine No.) of the controller corresponding to the
selected port. The CPU serial address can be anything from 1 to 63. It must match the
communications settings in the Communications Module of the controller. Each con-
troller can be assigned a device name. The device name can be up to 20 characters
long.

b)

Controller Setting

Dialog Box for CP-218

Specify the IP address of the controller corresponding to the selected port.
Also, specify the port number to be used.
Specify the protocol to be used. (Select from TCP or UDP.) The above settings must
match the communications settings of the Communications Module of the controller.
Each controller can be assigned a device name. The device name can be up to 20
characters long.