beautypg.com

A.1.3 parameter details, Process result (param00), Status (param01) – Yaskawa MP900 Series MPLOGGER User Manual

Page 119: Bit assignments request

background image

Appendix A

A.1.3 Parameter Details

A-4

A.1.3

Parameter Details

„

Process Result (PARAM00)

Outputs the process result to the upper bytes. The lower bytes are for system analysis.

• 00xx: BUSY
• 10xx: COMPLETE
• 8xxx: ERROR

„

Status (PARAM01)

Outputs the status of the transmitter.

Bit Assignments

REQUEST

1 = Request
0 = Notification that Reception is Completed

Error

code

Error

Description

81xx

Function code error

An invalid function code was sent or received.

82xx

Address setting error

The data address, coil offset, input relay offset, input register offset, or
holding register offset is out of range.

83xx

Data size error

The amount of sent or received data is out of range.

84xx

Circuit number setting error

The circuit number is out of range.

85xx

Channel number setting error

The channel number is out of range.

86xx

Station address error

The station number is out of range.

88xx

Transmitter error

An error response was returned from the transmitter.

89xx

Device option error

An invalid device was selected.