A.1.3 parameter details, Process result (param00), Status (param01) – Yaskawa MP900 Series MPLOGGER User Manual
Page 119: Bit assignments request

Appendix A
A.1.3 Parameter Details
A-4
A.1.3
Parameter Details
Process Result (PARAM00)
Outputs the process result to the upper bytes. The lower bytes are for system analysis.
• 00xx: BUSY
• 10xx: COMPLETE
• 8xxx: ERROR
Status (PARAM01)
Outputs the status of the transmitter.
Bit Assignments
REQUEST
1 = Request
0 = Notification that Reception is Completed
Error
code
Error
Description
81xx
Function code error
An invalid function code was sent or received.
82xx
Address setting error
The data address, coil offset, input relay offset, input register offset, or
holding register offset is out of range.
83xx
Data size error
The amount of sent or received data is out of range.
84xx
Circuit number setting error
The circuit number is out of range.
85xx
Channel number setting error
The channel number is out of range.
86xx
Station address error
The station number is out of range.
88xx
Transmitter error
An error response was returned from the transmitter.
89xx
Device option error
An invalid device was selected.
PARAMETER
COMMAND
RESULT
REQUEST
F
7
8
6
5
4
3
2
1
0
9
A
B
C
D
E