Specifications
49
12.0 S
PECIFICATIONS
Figure 36 XDF model numbers
Table 10
Physical specifications
Dimensions
XDFS141
Self- Contained,
Air Cooled XDF
XDFW141
Water/Glycol
Cooled XDF
Height, In. (mm)
Overall
82-1/4 (2089)
79-3/4 (2026)
Cabinet Only
79-3/4 (2026)
79-3/4 (2026)
Fan Guard
2-1/2 (57)
N/A
Equipment Rack Area
36U
42U
Width, In. (mm)
Overall
34-1/8 (867)
EIA Nominal
19 (483)
Inside Dimension
17-13/16 (452)
Depth, In. (mm)
Overall
49-1/2 (1257)
Mounting Depth, adjustable, minimum
24-3/8 (620)
Mounting Depth, adjustable, maximum
32-11/32 (821)
Weight, Lb. (kg)
Cabinet Only
710 (322)
668 (303)
Equipment Capacity
1200 (544)
XDF
S
14
1
0
1
0
Liebert Extreme Heat
Density
Foundation Enclosure
S = Self-Contained,
Air Cooled
W = Water Cooled
0 = None
A = GXT2-1000
B = GXT2-1500
C = GXT2-2000
D = GXT2-3000
E = GXT2-700
F = PS1000RT2
G = PS1440RT2
H = PS2200RT2
I = PS3000RT2
K = GXT2-2700 (*)
L = GXT2-6000 (*)
M = GXT2-10000 (*)
(*) 208VAC models
= 14kW
1 = 120V-1ph-60HzkW
and 208V-3ph-60Hz
0 = None
1 = Module
Included
0 = None
1 = Module
Included
Model
Model Type
Cooling
Capacity
Input
Power
UPS
Enclosure
Total Load
Monitoring
Condensate
Pump