XDF Components

13

3.2

Coolant Source—Water/Glycol Models

The XDF water/glycol cooled models may be connected to either of two types of coolant sources:

• a closed-loop water system (cooling tower)
• a drycooler loop

3.2.1 Closed-Loop Water System

A closed water supply system is required for efficiency and to protect the equipment from particles

and other contaminants that might obstruct the system’s piping.

Figure 10 Water/glycol XDF supplied by closed-loop water system

!

CAUTION

Risk of dirt and debris contamination. May cause condenser clogging.
Do not install the XDF on an open-loop water supply system. Debris carried by the fluid will

clog the XDF’s brazed plate condenser.

Closed-Loop

Water System

Hose Bibs

XDF

Supply

Line

XDF

Return

Line