AINTENANCE

11.1 Periodic Maintenance

The Liebert XDF requires very little maintenance. The XDF’s condenser coil must be inspected peri-

odically to determine the necessary cleaning interval based on conditions at the installation site.

Depending on site conditions, the coil may require cleaning as often as twice a month or as seldom as

twice per year. If the coil becomes dirty and clogged, it should be vacuumed with a soft bristle brush

or cleaned with compressed air.

Table 9

Troubleshooting

Problem

Cause

Solution

XDF system not cooling

No Power

Confirm unit is plugged in and the building breaker has not

tripped.

Clogged condenser coil

Clean coil. See 11.1 - Periodic Maintenance.

Hot Gas bypass valve set

incorrectly

Contact Liebert Technical Support at 800-543-2378.

Refrigerant loss

Verify leak. If refrigerant system needs repaired, contact

Liebert Technical Support at 800-543-2378.

Fans blowing warm air

Airflow is blocked at the intake

or exhaust.

Remove airflow obstructions from the front and rear of the

enclosure. Ensure the cabinet has at least 36" (915mm)

front, rear and overhead clearance. (Water/glycol models

do not require overhead clearance.) Open XDF’s doors and

let compressor cool. Plug in XDF and verify compressor is

energized.

Compressor trips on thermal

overload

Open XDF doors and let compressor cool. Plug in XDF and

verify compressor is energized.

Faulty Compressor

Contact Liebert Technical Support at 800-543-2378.

Water leaking from inside

the cabinet

Cabinet not level or internal

drain line clogged

Ensure that the enclosure rests on a level surface. The

cabinet must be level to ensure proper operation. Verify

condensate drain is attached to drain and the drain line has

the proper pitch (see 4.5.4 - Condensate Drain

Connection).

Excessive vibration or

noise

Defective motor in blower or

shipping damage

Contact Liebert Technical Support at 800-543-2378.

Cabinet is excessively hot

Electronic equipment not

positioned for optimum cabinet

airflow

Rearrange the equipment as illustrated in 4.7 - Equipment

Layout.

Compressor is overloaded

Verify the UPS load does not exceed XDF’s capacity. If no

UPS, verify equipment load does not exceed the XDF’s

rating.

Heat not rejected from room

Verify that XDF is in room with air circulation and heat

rejected from unit is sufficiently removed.

XDF system not cooling

Confirm unit is plugged in and the building breaker has not

tripped. Check setpoints on iCOM controller.

Cabinet not sealed

Check cable entry points, and verify doors and side panels

are closed. Reposition wires to prevent air leak, or fix or

replace damaged gaskets.

Audible alarm and cabinet

is excessively hot

iCOM control module has

detected an abnormal condition

Silence alarm on the iCOM module. See solutions for “XDF

system not cooling,” “Fans blowing warm air” and “Cabinet

is excessively hot causes” to determine course of action.