ProSoft Technology PLX8X-MNET-61850 User Manual
Page 140

Reference
PLX8x-MNET-61850 ♦ Communication Gateway
User Manual
Modbus TCP/IP to IEC 61850
Page 140 of 228
ProSoft Technology, Inc.
May 14, 2014
6.1.3 Specifications - IEC 61850 Client
Supports up to
20 IEDs
Send commands from the PLC to the IED using Control Types
o
Direct-with-normal-security
o
Select Before Operate (SBO)-with-normal-security
o
Direct-with-enhanced-security
o
Select Before Operate (SBO)-with-enhanced-security
ACSI Basic Conformance
SCSMs supported
SCSM: IEC 61850-8-1 used
ACSI Model Conformance
Reporting
Buffered Report Control Block (BRCB)
Unbuffered Report Control Block (URCB)
GOOSE:
entryID, DataReflnc
Control
Direct-with-normal-security
SBO-with-normal-security
Direct-with-enhanced-security
SBO-with-enhanced-security
Logical Nodes
IEC 61850 Logical Nodes, including Logical
Nodes for Hydro Power Plants and Logical
Nodes for Wind Power Plants
Configurable Parameters
MMS Command Delay
Status Data
Status available per node
Report and GOOSE status available
High-level status data available from Modbus
TCP/IP Client ( for example PLC)
6.1.4 Specifications
–SNTP/NTP Client
The gateway supports a Simple Network Time Protocol (SNTP/NTP) client
service that can synchronize the gateway’s time by periodic updates to a Co-
ordinated Universal Time (UTC) system. The user can configure the SNTP/NTP
server details in ProSoft 61850 Configuration Manager. The resolution of the time
is in milliseconds (ms).
Configurable Parameters:
SNTP/NTP server synchronization rate (in minutes)
SNTP/NTP Address