MVI-ADM ♦ 'C' Programmable
Side-Connect API Library Functions
'C' Programmable Application Development Module
Developer's Guide
ProSoft Technology, Inc.
Page 311 of 342
February 20, 2013
An attempt to read past the end of a data table file will result in a return code of
MVISC_ERR_XFERFAIL or MVISC_ERR_PCCCFAIL. If the PLC is in RUN mode when this read
is attempted, the PLC-5 will be faulted. Care should be taken not to exceed the boundaries of the
PLC-5 data tables. See MVIsc_GetPLCFileInfo to determine valid data table boundaries.
Return Value
MVISC_SUCCESS
The data was read successfully
MVISC_ERR_NOACCESS
handle does not have access
MVISC_ERR_BADPARAM
Parameter contains invalid value
MVISC_ERR_PLCTIMEOUT
PLC-5 did not respond
MVISC_ERR_XFERFAIL
PLC-5 returned an error
MVISC_ERR_PCCCFAIL
PCCC error occurred
Example
HANDLE Handle;
float f[3];
WORD scantime;
short acc;
int rc;
/* Read 3 floating-point values starting at element 5 of float file 8 (F8:5 -
F8:7), asynchronously */
rc = MVIsc_ReadPLC(Handle, f, 8, 5, 0, 3, MVISC_DTYP_FLOAT,
MVISC_ASYNC_ACCESS);
if (rc != MVISC_SUCCESS)
printf("ERROR: MVIsc_ReadPLC failed");
/* Read the last program scan time from the status file (S2:8), synchronously
*/
rc = MVIscReadPLC(Handle, &scantime, 2, 8, 0, 1, MVISC_DTYP_WORD,
MVISC_SYNC_ACCESS);
if (rc != MVISC_SUCCESS)
printf("ERROR: MVIsc_ReadPLC failed");
/* Read the accumulated value from timer 2 of timer file 4 (T4:2.ACC),
synchronously */
rc = MVIscReadPLC(Handle, &acc, 4, 2, MVISC_SUBEL_T_ACC, 1,
MVISC_DTYP_WORD, MVISC_SYNC_ACCESS);
if (rc != MVISC_SUCCESS)
printf("ERROR: MVIsc_ReadPLC failed");