beautypg.com

5 wiring the fault alarm contact – PLANET IVC-2002 User Manual

Page 20

background image

20

3.5 Wiring the Fault Alarm Contact

The fault alarm contacts are in the middle of the terminal block
connector as the picture shows below. Inserting the wires, the
Industrial Ethernet Extender will detect the fault status of the power
failure and then forms an open circuit. The following illustration shows
an application example for wiring the fault alarm contacts.

Insert the wires into the fault alarm contacts

Note

1. The wire gauge for the terminal block should be in

the range between 12 ~ 24 AWG.

2. Alarm relay circuit accepts up to 30V, max. 3A

currents.