2.5

CURRENT MONITORING (-1URC AND -1URY MODELS ONLY)

Monitored Output Current (Amps) = Voltage drop across Rs (Volts) x Rs (Ohms), where voltage
drop across Rs (see Table 2-3) is measured across ± IMON pins (requires millivoltmeter, range
0 to 200mV). Accuracy of voltage drop across Rs (representing monitored output current) is
±10%; contact Kepco if greater accuracy is required. See Figure 2-16 for typical configuration.

I/O connector pins designated for use for current monitoring are as follows:

I/O Connector

+IMON

–IMON

Slot 1

PS1, PS2

Pin 15

Pin 3

Slot 2

PS1, PS2

Pin 13

Pin 2

Slot 3

PS3, PS4

Pin 15

Pin 3

Slot 4

PS3, PS4

Pin 13

Pin 2

CAUTION:

There is no isolation between ±IMON, alarm circuit and d-c output. +IMON is

also the –V output of the HSF power supply. For -1URY models, +IMON may
also be used for –RC.

FIGURE 2-16. USING CURRENT MONITORING (TYPICAL), -1URC AND -1URY MODELS ONLY

TABLE 2-3. SENSE RESISTOR VALUES

SERIES

3.3V Model

5V Model

12V Model

15V Model

24V Model

28V Model

48V Model

HSF -1UR 50W

0.01 Ohm

0.01 Ohm

0.02 Ohm

0.03 Ohm

0.05 Ohm

0.05 Ohm

0.1 Ohm

HSF -1UR 100W

5 mOhm

5 mOhm

10 mOhm

20 mOhm

20 mOhm

30 mOhm

50 mOhm

HSF -1UR 150W

2.5 mOhm

2.5 mOhm

10 mOhm

10 mOhm

20 mOhm

20 mOhm

30 mOhm