TROUBLESHOOTING

If the meter is not working as expected, refer to the troubleshooting tips
on page 68.

Determining Software Version

To determine the software version of the meter:

1. Go to the Information menu (info) in the Advanced Features

menu and press the Enter/Ack button.

2. Press

Enter/Ack to access the software number (SFT), version

(UER), and serial number (Sn) information. Write down the
information as it is displayed. Continue pressing Enter/Ack until
all the information is displayed.

Reset Meter to Factory Defaults

When the parameters have been changed in a way that is difficult to
determine what is happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter

the

Advanced features menu. See Advanced Features Menu,

page 52.

2. Press

Up arrow several times to go to the Information menu.

3. Press and hold Right arrow/Reset for five seconds, then press

Enter/Ack when display flashes reset.
Note: If Enter/Ack is not pressed within three seconds, display
returns to meter Run.

4. The meter loads the factory default settings, and goes through an

initialization sequence (same as on power-up).

info

Press and hold
for 3 seconds

reset

Press and hold
for 5 seconds

Flashing

Display

Meter

Reinitializes