beautypg.com

Relays – Precision Digital PD865 User Manual

Page 11

background image

PD865 Snooper Modbus

Serial Input Meter

Instruction Manual

11

Relays

RATING

Standard: 2 relays, SPST (Form A)
Optional: 2 relays, SPDT (Form C)
All relays are rated 3 A @ 30 VDC or 3 A @ 250 VAC,
resistive loads.

ELECTRICAL
NOISE
SUPPRESSION

A suppressor (snubber) should be connected to each relay
contact switching inductive loads to prevent disruption to
the microprocessor’s operation. Recommended suppressor
value: 0.01 µF/470

, 250 VAC (PDX6901).

DEADBAND

0-100% of full scale, user selectable

HIGH OR LOW
ALARM

User may program any alarm for high or low trip point.

RELAY
OPERATION

Automatic (non-latching)
Latching
Pump alternation control (up to 4 relays)

RELAY RESET

User selectable via front panel buttons or Modbus control

Automatic reset only (non-latching)

Automatic + manual reset at any time (non-latching)

Manual reset only, at any time (latching)

Manual reset only after alarm condition has cleared (latching)

Automatic reset: Relays will automatically reset when the
input passes the reset point.

Manual reset: Front panel ACK button. Pressing ACK
resets all manually resettable relays.

TIME DELAY

0 to 199 seconds, on and off delays
Programmable and independent for each relay

FAIL-SAFE
OPERATION

Programmable
Independent for each relay

COMMUNICA-
TIONS BREAK

No change, Relay on, or Relay off.
Controls the condition the relay goes to when a slave
device does not reply (Available also in Slave mode v1.1 &
up).

AUTO
INITIALIZATION

When power is applied to the meter, relays will reflect the
state of the input to the meter.

Fail-safe operation: relay coil is energized in non-alarm condition. In case of
power failure, relay will go to alarm state.