beautypg.com

Pd865 snooper modbus, Serial input meter instruction manual – Precision Digital PD865 User Manual

Page 31

background image

PD865 Snooper Modbus

Serial Input Meter

Instruction Manual

31

Master Mode (nmastr)
The Master mode contains the following submenus: select which
Function Code to use, the number of PVs to poll, the slave IDs and
register numbers, the type and format of data for PV1, the slave Polling
time and Response timeout.

Press Enter/Ack to

Make Selections

Press Up Arrow to

Scroll Through Choices

Press Menu to Exit at

any Time

Press Right Arrow to display and
change the setting for the number of
digits used for the Register Number.

t-resp

Enter Response

Timeout Value

t-poll

Enter Polling

Time Value

nmastr

funCod

fun 03

fun 04

data.1

short

long

float

binary

bcd

unsigd

signed

1234

4321

2143

3412

The last two Byte-Order settings are not

available for Short Integer data types.

reg.nbr

Enter Register
Number Value

5 dig

6 dig

SLAv.1d

1 d-pv1

Enter Slave ID

for PV1

PU.nbr

Enter Number

of Process

Variables

reg.Pv1

The Master ignores the decimal point setting for most slave devices that
specify a Short or Long integer. For example, a slave that is displaying
12.34 is read as 1,234. Floating point data may or may not utilize the
decimal point. Refer to the slave’s operating manual to make sure.

The Register Number range is based on the Function Code and the
number of digits selected. See the following table.

Function Code

5 Digit

6 Digit

03

40001 – 49999

400001 – 465536

04

30001 – 39999

300001 – 365536