Precision Digital PD865 User Manual
Page 19

PD865 Snooper Modbus
Serial Input Meter
Instruction Manual
19
Relay Connections 
Connections to the two, standard Form A relays, are made to the 
connector labeled RLY1 and RLY2. See Figure 5. Connections to the 
two optional Form C relays are made to the six-terminal connector 
labeled RELAY3 and RELAY4. 
Figure 7: Standard and Optional Relay Connectors
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching 
inductive loads to prevent disrupting the microprocessor’s operation. The 
suppressors also prolong the life of the relay contacts. Suppression can be 
obtained with resistor-capacitor (RC) networks assembled by the user or 
purchased as complete assemblies. Refer to the following circuits for RC network 
assembly and installation: 
L
O
A
D
or
Figure 8: AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1
 for each volt across the contacts.
C: 0.5 to 1 µF for each amp through closed contacts. 
 
Notes:
1.
Use capacitors rated for 250 VAC.
2.
RC networks may affect load release time of solenoid loads. Check to 
confirm proper operation. 
3.
Install the RC network at the meter's relay screw terminals. An RC network 
may also be installed across the load. Experiment for best results. 
4.
For low voltage DC loads, place a diode across the load with a reverse 
breakdown voltage two to three times the circuit voltage and a forward 
current at least as large as the load current. Shown in 
Figure 9
