Pd865 snooper modbus, Serial input meter instruction manual – Precision Digital PD865 User Manual

Page 48

background image

PD865 Snooper Modbus

Serial Input Meter

Instruction Manual

48

Relay Operation After Communications Break

When a Master meter fails to receive a reply from the slave it is called a
Communications Break. The relays can be programmed to react to this
event by going On, Off, or No Action. After communications is restored
the relays are turned off or on based on their operating mode and their
set and reset points, without regard to their prior state. This is similar to
the auto initialization on power up. Below is a diagram showing three
examples.
The same is true for a meter set up to operate in Snooper mode.

Relay 1

Manual mode

Relay 2

Manual mode

Input

de-energized

energized

Relay 3

Auto mode

Relay 1 Set

Relay 1 to 3

Reset

Relay 2 Set

Relay 3 Set

Communications

Break

Communications
Restored

No Serial

Communications

Communications

Break: No Action

Communications

Break: Relay "on"

Communications

Break: Relay "on"