beautypg.com

Analog input modules -6, 3 analog, Input modules -6 – Emerson ROC827 User Manual

Page 76: 3 wiring i/o modules, 3 analog input modules

background image

ROC827 Instruction Manual

Issued Mar-06

Input/Output Modules

4-6

6.

Replace the wire channel cover.

4.2.3 Wiring I/O Modules

All modules have removable terminal blocks for convenient wiring and
servicing. The terminal blocks can accommodate a wide range of wire
gauges (12 AWG or smaller).

Caution

Failure to exercise proper electrostatic discharge precautions, such as
wearing a grounded wrist strap may reset the processor or damage
electronic components, resulting in interrupted operations.

To connect the wire to the removable block compression terminals:

1.

Bare the end (¼ inch maximum) of the wire.

2.

Insert the bared end into the clamp beneath the termination screw.

3.

Tighten the screw.

The ROC827 should have a minimum of bare wire exposed to prevent
short circuits. Allow some slack when making connections to prevent
strain.

Note

: All modules have removable terminal blocks for convenient wiring

and servicing. Twisted-pair cable is recommended for I/O signal wiring.
The removable terminal blocks accept 12 AWG or smaller wire.

4.3

Analog Input Modules

The four Analog Input (AI) channels are scalable, but typically measure
either:

ƒ 4- to 20-mA analog signal, with the use of a precision resistor

(supplied).

ƒ 1 to 5 Volts dc signal.

If required, you can calibrate the low end of the analog signal to zero.

You can configure the AI (+T) module as either 12 or 24 Volt dc using
jumper J4 on the I/O module (see Figure 4-4). The AI modules can
provide isolated +12 Volt dc or +24 Volt dc field transmitter power on a
per-module basis. For example, one module can provide +12 Volts dc for
powering low power analog transmitters, while another module in the
same ROC827 can provide +24 Volts dc for powering conventional 4- to
20-mA transmitters. Refer to Figure 4-5: