beautypg.com

Checklists -2, 2 checklists -2 – Emerson ROC827 User Manual

Page 114

background image

ROC827 Instruction Manual

Issued Mar-06

Troubleshooting

6-2

6.2 Checklists

If the LEDs do not display:

ƒ By default, LEDs on the communication modules and I/O modules

enter Sleep mode after five minutes.

ƒ To turn the LEDs on, press the LED button located on the CPU for

one second.

Note

: Using the ROCKLINK 800 software, you can disable this feature

so that the LEDs always remain on.

6.2.1 Serial Communications

If you are experiencing troubles with a serial communications connection
(LOI, EIA-232, EIA-422, or EIA-485):

ƒ Check to make sure power is applied to the ROC827 unit. Check the

ON/OFF jumper, the wiring connections at CHG+ and CHG–, and the
wiring at the power source.

ƒ Check the wiring to the termination block or connector. Refer to

Chapter 5, Communications.

ƒ Check the communication port settings using ROCLINK 800

Configuration software. Refer to ROCLINK 800 Configuration
Software User Manual
(Form A6121).

6.2.2 I/O Point

If you are experiencing troubles with an I/O point (Analog Input, Analog
Output, Discrete Input, Discrete Output, Pulse Input, RTD Input, or
Thermocouple Input):

ƒ Check (using ROCLINK 800 software) to see how the channel is

configured.

ƒ If the configuration looks correct, then follow the procedure for

troubleshooting that type of I/O (refer to Chapter 6, sections 3 through
10).

ƒ If a module does not function correctly, determine if the problem is

with the field device or the module.

ƒ Check a module suspected of being faulty for a short circuit between

its input or output terminals. If a terminal not directly connected to
ground reads 0 (zero) when measured with an ohmmeter, the module
is defective and must be replaced.

Note

: Return faulty modules to your local sales representative for

repair or replacement.