SPI9000 Inverter Unit FI9 – FI14 User Manual

MN04004002E

For more information visit: www.EatonElectrical.com

A-3

September 2006

Table A-1: Fault Codes (Continued)

Programmable.

“A” faults only.

Fault
Code Fault

Possible Cause

Solution

31

IGBT Temperature
(hardware)

IGBT inverter bridge
overtemperature protection detected
a short term overload current that is
too high.

Check loading.
Check motor size.

32

Fan Cooling

Cooling fan of the inverter does not
start, when ON command is given.

Contact your Cutler-Hammer
distributor.

34

CAN Bus
Communication

Sent message not acknowledged.

Ensure that there is another device

on the bus with the same
configuration.

36

Control Unit

Control unit cannot control power
unit and vice versa.

Change control unit.

37

Device Change
(same type)

• Option board or control unit

changed

• Option board of different type or

drive with different power rating

Reset
Note: No fault time data record.

38

Device Added
(same type)

• Option board or drive added
• Drive with same power rating or

same type of board added

Reset
Note: No fault time data record.

39

Device Removed

• Option board removed
• Drive removed

Reset
Note: No fault time data record.

40

Device Unknown

Unknown option board or drive.

Contact your Cutler-Hammer

distributor.

41

IGBT Temperature

IGBT Inverter Bridge
overtemperature protection has
detected a short term overload
current that is too high.

Check loading.
Check motor size.

42

Brake Resistor
Overtemperature

Brake resistor overtemperature
protection detected braking that is
too heavy.

Set the deceleration time longer.
Use external brake resistor.

43

Encoder Fault

Note: See the exceptional fault data
record on Page 5-12. Additional
codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are

missing

4 = Encoder reversed

Check encoder channel connections.
Check the encoder board.

44

Device Change
(different type)

• Option board or control unit

changed

• Option board of different type or

drive with different power rating

Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.

45

Device Added
(different type)

• Option board or device added
• Option board of different type or

drive with different power rating
added

Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.