Table 1-4: Technical Information, continued

Description

Specification

Ambient Conditions, continued

Vibration
EN 50178/EN 60068-2-6

5 – 150 Hz
Displacement amplitude: 1 mm (peak) at 3 – 15.8 Hz
Maximum acceleration amplitude: 1G at 15.8 – 150 Hz

Shock
EN 50178, EN 60068-2-27

UPS Drop Test (for applicable UPS weights)
Storage and shipping: Maximum 15G, 11 ms (in package)

Cooling Capacity Required

P

loss

[kW] approx. P

mat

[kW] x 0,025

Cooling Air Required

FI9, 677 cfm; FI10, 824 cfm;
FI12, 1648 cfm; FI13, 2472 cfm

Unit Enclosure Class

IP00

EMC (at Default Settings)

Immunity

Fulfill all EMC immunity requirements

Safety

CE, UL, CUL
EN 61800-5-1 (2003) See unit nameplate for more detailed approvals.

Control Connections

Analog input voltage

0 to +10V, R

i

= 200kΩ

Ω

Ω

Ω, (–10V to +10V joystick control)

Resolution 0.1%; Accuracy ±1%

Analog input current

0(4) – 20 mA, R

i

= 250Ω

Ω

Ω

Ω differential

Digital inputs (6)

Positive or negative logic; 18 – 30V DC

Auxiliary voltage

+24V, ±15%, max. 250 mA

Output reference voltage

+10V, +3%, max. load 10 mA

Analog output

0(4) – 20mA; R

L

max. 500Ω

Ω

Ω

Ω

Resolution 10 bits; Accuracy ±2%

Digital outputs

Open collector output, 50 mA/48V

Relay outputs

2 programmable change-over relay outputs
Switching capacity: 24V DC/8A, 250V AC/8A, 125V DC/0.4A
Minimum switching load: 5V/10 mA

Protections

Overvoltage Protection
Undervoltage Protection

500V inverters: 911V DC; 690V inverters: 1200V DC
500V inverters: 333V DC; 690V inverters: 460V DC

Ground Fault Protection

In case of ground fault in motor or motor cable, only the inverter is
protected.

Motor Phase Supervision

Trips if any of the output phases are missing.

Overcurrent Protection

Yes

Unit Overtemperature Protection Yes

Motor Overload Protection

Yes

Motor Stall Protection

Yes

Motor Underload Protection

Yes

Short Circuit Protection of +24V
and +10V Reference Voltages

Yes