Eaton Electrical SPI9000 User Manual
Page 17
![background image](/manuals/81732/17/background.png)
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
For more information visit: www.EatonElectrical.com
1-7
September 2006
Table 1-4: Technical Information, continued
Description
Specification
Ambient Conditions, continued
Vibration
EN 50178/EN 60068-2-6
5 – 150 Hz
Displacement amplitude: 1 mm (peak) at 3 – 15.8 Hz
Maximum acceleration amplitude: 1G at 15.8 – 150 Hz
Shock
EN 50178, EN 60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: Maximum 15G, 11 ms (in package)
Cooling Capacity Required
P
loss
[kW] approx. P
mat
[kW] x 0,025
Cooling Air Required
FI9, 677 cfm; FI10, 824 cfm;
FI12, 1648 cfm; FI13, 2472 cfm
Unit Enclosure Class
IP00
EMC (at Default Settings)
Immunity
Fulfill all EMC immunity requirements
Safety
CE, UL, CUL
EN 61800-5-1 (2003) See unit nameplate for more detailed approvals.
Control Connections
Analog input voltage
0 to +10V, R
i
= 200kΩ
Ω
Ω
Ω, (–10V to +10V joystick control)
Resolution 0.1%; Accuracy ±1%
Analog input current
0(4) – 20 mA, R
i
= 250Ω
Ω
Ω
Ω differential
Digital inputs (6)
Positive or negative logic; 18 – 30V DC
Auxiliary voltage
+24V, ±15%, max. 250 mA
Output reference voltage
+10V, +3%, max. load 10 mA
Analog output
0(4) – 20mA; R
L
max. 500Ω
Ω
Ω
Ω
Resolution 10 bits; Accuracy ±2%
Digital outputs
Open collector output, 50 mA/48V
Relay outputs
2 programmable change-over relay outputs
Switching capacity: 24V DC/8A, 250V AC/8A, 125V DC/0.4A
Minimum switching load: 5V/10 mA
Protections
Overvoltage Protection
Undervoltage Protection
500V inverters: 911V DC; 690V inverters: 1200V DC
500V inverters: 333V DC; 690V inverters: 460V DC
Ground Fault Protection
In case of ground fault in motor or motor cable, only the inverter is
protected.
Motor Phase Supervision
Trips if any of the output phases are missing.
Overcurrent Protection
Yes
Unit Overtemperature Protection Yes
Motor Overload Protection
Yes
Motor Stall Protection
Yes
Motor Underload Protection
Yes
Short Circuit Protection of +24V
and +10V Reference Voltages
Yes