SPI9000 Inverter Unit FI9 – FI14 User Manual

MN04004002E

For more information visit: www.EatonElectrical.com

4-7

September 2006

Table 4-3: Control I/O Terminal Signals on Option Board A2

Table 4-4: Control I/O Terminal Signals on Option Board A3

Digital Input Signal Inversions

The active signal level depends on which potential the common inputs CMA and CMB
(terminals 11 and 17) are connected to. The alternatives are either +24V or ground (0V). See
Figure 4-9.

We recommend the use of positive logic in all control connections of the inverter. If negative
logic is used, additional appropriate measures are needed to meet the safety regulation
requirements.

The 24 volt control voltage and the ground for the digital inputs and the common inputs
(CMA, CMB) can be either internal or external.

Figure 4-9: Positive/Negative Logic

Positive logic (+24V is the active signal) = Input is active when the switch is closed.

Negative logic (0V is the active signal) = Input is active when the switch is closed.

Requires setting of jumper X3 to position “CMA/CMB isolated from ground.”

OPTA2

21

RO1/1

Relay output 1

Switching capacity

24V DC/8A

250V AC/8A
125V DC/0.4A
5V/10 mA

22

RO1/2

23

RO1/3

Min. switching load

24

RO2/1

Relay output 2

Switching capacity

24V DC/8A

250V AC/8A
125V DC/0.4A
5V/10 mA

25

RO2/2

26

RO2/3

Min. switching load

OPTA3

21

RO1/1

Relay output 1

Switching capacity

24V DC/8A

250V AC/8A
125V DC/0.4A
5V/10 mA

22

RO1/2

23

RO1/3

Min. switching load

24

RO2/1

Relay output 2

Switching capacity

24V DC/8A

250V AC/8A
125V DC/0.4A
5V/10 mA

25

RO2/2

26

RO2/3

Min. switching load

28

TI1+

Thermistor input

29

TI1-

DIN1

+24V

DIN2

DIN3

CMA

Ground

DIN1

Ground

DIN2

DIN3

CMA

+24V