beautypg.com

Eaton Electrical SPI9000 User Manual

Page 34

background image

SPI9000 Inverter Unit FI9 – FI14 User Manual

3-10

For more information visit: www.EatonElectrical.com

MN04004002E

September 2006

Fuses, 640 – 1100V DC Inverters

Table 3-3: Fuses Used in 640 – 1100V DC Inverters

Information about fuses:

gR fuses are designed to protect the device against both overcurrent and short circuits.

aR fuses protect the cables of the device against short circuits.

gG fuses are generally used to protect cables against overcurrent and short circuits.

Nominal
Current

Frame

Bussman aR
Fuse Type

Fuse Size

Fuse U

n

(V)

Fuse I

n

(A)

No. of Fuses

100

FI9

170M4199

1SHT

1250

400

2

125

FI9

170M4199

3SHT

1250

400

2

144

FI9

170M4199

3SHT

1250

400

2

170

FI9

170M4199

3SHT

1250

400

2

208

FI10

170M6305

3SHT

1250

700

2

261

FI10

170M6305

3SHT

1250

700

2

325

FI10

170M6277

3SHT

1250

1000

2

325

FI10

170M6277

3SHT

1250

1000

4

385

FI12

170M6305

3SHT

1250

700

4

460

FI12

170M6305

3SHT

1250

700

4

502

FI12

170M6305

3SHT

1250

700

4

590

FI12

170M6277

3SHT

1250

1000

4

650

FI12

170M6277

3SHT

1250

1000

4

650

FI12

170M6277

3SHT

1250

1000

4

820

FI13

170M6305

3SHT

1250

700

6

920

FI13

170M6277

3SHT

1250

1000

6

1030

FI13

170M6277

3SHT

1250

1000

6

1300

FI14

170M6277

3SHT

1250

1000

2 x 6

1500

FI14

170M6277

3SHT

1250

1000

2 x 6

1900

FI14

170M6277

3SHT

1250

1000

2 x 6