Eaton Electrical SPI9000 User Manual
Page 34
SPI9000 Inverter Unit FI9 – FI14 User Manual
3-10
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Fuses, 640 – 1100V DC Inverters
Table 3-3: Fuses Used in 640 – 1100V DC Inverters
Information about fuses:
gR fuses are designed to protect the device against both overcurrent and short circuits.
aR fuses protect the cables of the device against short circuits.
gG fuses are generally used to protect cables against overcurrent and short circuits.
Nominal
Current
Frame
Bussman aR
Fuse Type
Fuse Size
Fuse U
n
(V)
Fuse I
n
(A)
No. of Fuses
100
FI9
170M4199
1SHT
1250
400
2
125
FI9
170M4199
3SHT
1250
400
2
144
FI9
170M4199
3SHT
1250
400
2
170
FI9
170M4199
3SHT
1250
400
2
208
FI10
170M6305
3SHT
1250
700
2
261
FI10
170M6305
3SHT
1250
700
2
325
FI10
170M6277
3SHT
1250
1000
2
325
FI10
170M6277
3SHT
1250
1000
4
385
FI12
170M6305
3SHT
1250
700
4
460
FI12
170M6305
3SHT
1250
700
4
502
FI12
170M6305
3SHT
1250
700
4
590
FI12
170M6277
3SHT
1250
1000
4
650
FI12
170M6277
3SHT
1250
1000
4
650
FI12
170M6277
3SHT
1250
1000
4
820
FI13
170M6305
3SHT
1250
700
6
920
FI13
170M6277
3SHT
1250
1000
6
1030
FI13
170M6277
3SHT
1250
1000
6
1300
FI14
170M6277
3SHT
1250
1000
2 x 6
1500
FI14
170M6277
3SHT
1250
1000
2 x 6
1900
FI14
170M6277
3SHT
1250
1000
2 x 6