Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
●
Press the STOP button on the keypad.
9. Perform the start-up tests without the motor being connected to the process. If this is
not possible, make sure that each test can be done safely prior to performing it. Inform
your co-workers of the tests.
●
Switch off the DC supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.
●
Connect the motor cable to the motor and to the motor cable terminals of the
inverter.
●
Make sure that all Start/Stop switches are in Stop positions.
●
Switch the supply voltage ON.
●
Repeat Test A or B in step 8.
10. Connect the motor to the process (if the start-up test was performed without the motor
being connected). Inform our co-workers of the tests.
●
Before running the tests, make sure that this can be done safely.
●
Repeat Test A or B in step 8.