NIC Setup and Testing

26

6.2

Testing the Network

“Ping” is a tool used to test the network. At the command prompt,

type, “ping

”. Ping will respond that it received a

reply from the card if the card is functioning properly on the network.
If the card is not functioning properly or is not connecting to the net-

work, ping will respond that the request it sent to the card has timed

out.
If the ping request times out, go to the Service Terminal to verify that

the card initialized the network when it powered up. If the card is sit-

ting at the text “Initializing network…” then the card has not con-

nected to the network. Hit to go into the Service Terminal.

Select No. 2 for the Network Interface Menu. Verify that you have the

boot mode set up correctly. If you choose a static IP Address, verify

that the IP Address is valid for your network.
If you obtain your network information from a BootP or DHCP server,

verify that the server is valid and that it is responding to requests.

Once the information has been verified, press to return to

the main menu and select “x” to exit out of the card. Then, reboot the

card. The card may be rebooted by pressing switch S1 on the card for

approximately 2 seconds until the DS9 link light turns off.
If the card still does not connect to the network, or ping still does not

receive a reply from the card, verify proper set up on the card itself.

DS4 should be illuminated if the card detects the network. Verify that

the network cable is connected to Ethernet port J3 and that the hub/

router/switch to which the card is connected is operating correctly.
Once this information is verified, reboot the card.

6.3

Service Terminal Troubleshooting

If the card does not bring up a Service Terminal, check link light DS9.

DS9 should be illuminated within approximately 0.5 seconds of appli-

cation of power. If DS9 is not illuminated and no other LED's are on,

verify that power has been applied to the card. If power has been

applied, verify wiring connected to TB3 is correct. TB3 should have

24VAC or 12 VDC applied. Reboot the card once the power to the card

has been verified.

6.4

SNMP Troubleshooting

If SNMP is not functioning, first make sure that the card powers up,

the Service Terminal is functioning and the card is connected to the

network (verified by using ping). If all of those conditions are met, ver-

ify that the community strings are set up correctly. To do this, go into

the Service Terminal and select number 3 for SNMP Communications.