Yaskawa SmartTrac AC1 User Manual
Page 38

SMART TRAC AC1
4-18
••
Smart Trac AC1 Installation Technical Manual TM 3554-000
Rated Voltage
400.0 VAC
11. Set the correct Nameplate voltage of the motor, using the
and
keys to scroll and the
key to move one decimal point to
the right.
Rated Voltage
460.0 VAC
12. Press
to store the value in memory. The message "Entry
Accepted" will appear briefly, followed by a return to the previous
"Rated Voltage" message.
Entry Accepted
Rated Voltage
400.0 VAC
13. Enter the current and the rest of the parameters following a similar
procedure to that of the motor nameplate voltage.
14. When all of the parameters are entered, execute Auto-Tuning:
15. Press the
. The message "Tuning Ready?" will appear.
Tuning Ready?
Press RUN key
16. Press
. The drive will first output current to the motor, then run
the motor at a high speed. During tuning, the following message will
appear.
Tune proceeding
XX Hz X.XX A
•
If no problems are encountered., the following message will
appear:
Tune Successful
•
If a problem occurs during Auto-Tuning execution, the "Tune
Aborted" message appears with a reason listed. See "Auto-Tuning
Faults and Corrective Actions".
Tune Aborted
"Reason"
17. If successful, record the settings for parameters E2-01 to E2-09. You
use the Programming Menu (see "Checking Motor Parameters").
18. Remove power from the Smart Trac AC1. Wait until the CHARGE
light goes out.