Network communications terminals <1 – Yaskawa VS606 V7 to V1000 User Manual
Page 8

Product Transition Guide
PL. V1000.01 Rev: 4/1/09
PL.V1000.01 Transition Guide 4/1/09
Page 8 of 38
Yaskawa Electric America, Inc.
Note: The current input for terminal A1 is not available on the V1000. Use terminal A2 for current input. <1>
Network Communications Terminals <1>
• "–" indicates that an equivalent terminal on the other unit does not exist.
FR
A1
Analog input 1
Voltage or current (not available on V1000 -
see Note) input (frequency reference)
0~+10 VDC (20 kW),
0 or 4~20 mA (250 kW) <1>
0~+10 VDC (20 kW) <1>
—
A2
Analog input 2
(frequency reference)
—
DC:0~+10 V (20 k
Ω)
0 or 4~20 mA (250 k
Ω)
(initial setting: 4-20 mA) <1>
FC
AC
Analog input common
0 V
—
HC
Hard wire baseblock common
—
+24 V (max. current 10 mA)
—
H1
Hard wire baseblock input
(EN954-1, category 3, Stop category 0) <1>
—
Open: Stop
Closed: Operation
MA
Multi-Function Digital Output
(N.O. Contact) (Fault)
Max. AC load:
250 VDC, 1 A max.
30 VDC, 1 A max. <1>
Max. load:
AC:250 V, 10 mA~1 A
DC:30 V, 10 mA~1 A
MB
Multi-Function Digital Output
(N.O. Contact) (Fault)
MC
Multi-Function Digital Output
(common)
P1
Open collector output 1
(during run)
Photocoupler +48 VDC, 50 mA or less Output
<1>
P2
Open collector output 2
(speed agree)
PC
Open collector output common
—
MP
Pulse output
(output frequency)
—
Max. 32 kHz
AM
Analog output
DC:0~+10 V, 2 mA max.
Resolution: 8 bit
DC:0~+10 V, 2 mA max.
Resolution: 1/1000 <1>
AC
Analog output GND
Serial
Communication
Terminals
Function
Signal Level
V7
V1000
V7
V1000
R+
R+
Receive +
RS-485/422 MEMOBUS
Protocol
Max. 19.2 kbps
RS-485/422 MEMOBUS
Protocol
Max. 115.2 kbps
R-
R-
Receive -
S+
S+
Transmit +
S-
S-
Transmit -
GND
IG
Shield connection, GND
—
0V
Control
Terminals
Function
Signal Level
V7
V1000
V7
V1000