Yaskawa VS606 V7 to V1000 User Manual
Page 28

Product Transition Guide
PL. V1000.01 Rev: 4/1/09
PL.V1000.01 Transition Guide 4/1/09
Page 28 of 38
Yaskawa Electric America, Inc.
Memobus
communication Speed
selection
n154
2
H5-02
3
V7
V1000
n154
→0
H5-02
→1
n154
→1
H5-02
→2
n154
→2
H5-02
→3
n154
→3
H5-02
→4
Memobus parity
selection
n155
0
H5-03
0
V7
V1000
n155
→0
H5-03
→1
n155
→1
H5-03
→2
n155
→2
H5-03
→0
Transmission wait time
n156
10 ms
H5-06
5 ms
RTS flow control
control on/off
n157
0
H5-07
1
V7
V1000
n157
→0
H5-07
→1
n157
→1
H5-07
→0
Motor code (for energy
saving)
n158
b8-04
E2-11,
o2-04
dep.
In the V7 the motor code sets the rated
power and the coefficient for energy
saving.
E2-11
In the V1000 the coefficient is set in
b8-04. It depends on the rated motor
power set in E2-11. E2-11 is
automatically adjusted during
autotuning.
Upper voltage limit for
energy saving at 60Hz
n159
120%
-
-
-
No setting available.
Upper voltage limit for
energy saving at 6Hz
n160
16%
Power detection hold
during voltage tuning
n161
10%
Power detection filter
time constant
n162
5
(20 ms)
b8-05
20 ms
PID output gain
n163
1.0
b5-10
1.0
PID feedback value
selection
n164
0
H3-09
2
V7
V1000
n164
→0
Term. A2:
H3-09
→0, H3-10→B
H3-10
0
n164
→1
Term. A2:
H3-09
→2, H3-10→B
n164
→2
Term. A2:
H3-09
→3, H3-10→B
n164
→3
– (no operator poti)
H6-01
0
n164
→4
n164
→5
H6-01 = 1
When terminal A2 is used always check
the position of DIP switch S1!
Braking resistor over
heat protection
(ERF type)
n165
0
L8-01
0
V7
V1000
n165
→0
L8-01
→0
n165
→1
L8-01
→1
Drive
Parameter
Function
V7
V1000
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value