V7 and v1000 specification differences – Yaskawa VS606 V7 to V1000 User Manual
Page 34

Product Transition Guide
PL. V1000.01 Rev: 4/1/09
PL.V1000.01 Transition Guide 4/1/09
Page 34 of 38
Yaskawa Electric America, Inc.
V7 and V1000 Specification Differences
Category
Feature
Item
V7
V1000
Power Section
Control Method
–
Sinewave PWM: V/f & OLV
Sinewave PWM: V/f & Current Vector
Power Section
Ratings
230v, 3ph.
0.125 to 10 HP
0.125 to 25 HP
Power Section
Ratings
460v, 3ph.
0.5 to 10 HP
0.5 to 25 HP
Power Section
Maximum Output
Frequency
–
400 Hz (800 Hz optional)
400 Hz (1000 Hz optional)
Power Section
Carrier Frequency
–
10 kHz (model dependent)
ND: 2 kHz; HD: 15 kHz (model dependent)
Power Section
F
c
Default (derate)
–
Constant
Swing PWM
Power Section
Braking Transistor
Circuit
–
Built-in to 10 HP
Built-in to 25 HP
Power Section
Short Circuit
Withstand Rating
–
18,000 A RMS Symmetrical
30,000 A RMS Symmetrical
Power Section
Control Method
–
IM only
IM / PM Control
Control Section
Digital Operator
Display
LED 4x 7 seg. (LCD option)
LED 5x 7 seg. (LCD option)
Control Section
Digital Operator
Number of Keys
6
8
Control Section
Copy Function
–
Built-in
Y-Stick USB copy unit option
Control Section
Microprocessor
–
Single
Dual
Control Section
Control Method
Pseudo-Closed Loop
No
Yes, w/ RP input
Control Section
Macro Applications
–
No
Yes
Control Section
Digital Input
Scan Rate
8 msec.
4 msec.
Control Section
Analog Input
Qty.
1 (Programmable)
2 (Programmable)
Control Section
Analog Input
Scan Rate
8 msec.
2 msec.
Control Section
Analog Input
Freq. Ref Voltage
15 Vdc
10.5 Vdc
Control Section
Analog Output
Scan Rate
8 msec.
2 msec.
Control Section
Pulse Input
Qty.
1 (Programmable)
1 (Programmable)
Control Section
Pulse Input
Input Frequency
33 kHz
33 kHz
Control Section
Pulse output
Qty.
1 (Programmable)
1 (Programmable)
Control Section
Pulse output
Output Frequency
1.44 kHz
33 kHz
Control Section
Digital Operator
Display
8 LED Indicators
6 LED Indicators
Control Section
Removable Terminal
Block
–
No
Yes (w / memory)
Control Section
Thermistor Input PTC
–
No
Yes
Control Section
2-Motor Control
–
No
Yes
Control Characteristics
Overload Capacity
–
150% for 1 min.
ND: 120% for 1 min.; HD: 150% for 1 min.
Control Characteristics
Starting Torque
–
150% @ 3 Hz (V/f)
150% @ 3 Hz (V/f),
200% @ 0.5 Hz (OLV)
Control Characteristics Speed Control Range
Open Loop for PM
N/A
1:10
Control Characteristics
Output Frequency
Resolution
–
0.01 Hz
0.001 Hz
Control Characteristics
Auto-Tuning
Automatic/OnLine
No
Yes, R1 and Rotational
Control Characteristics
Elapse Time
–
No
Yes (Power up or Run)
Control Characteristics
Fault Storage
–
Last 4
Last 10 w / Elapsed Time Meter
Control Characteristics
Fault Record
–
No Trace Data Points
15 Trace Data Points
Control Characteristics
High Current Alarm
HCA
No
Yes, 150%
Control Characteristics
OV Suppression
–
Option- CASE
Standard
Control Characteristics
Torque Detection
–
Over-Torque
Over and Under-Torque