PL.V1000.01 Transition Guide 4/1/09
Page 23 of 38
Yaskawa Electric America, Inc.
Product Transition Guide
PL. V1000.01 Rev: 4/1/09
Analog input FR (A1)
gain
n060
100%
H3-03
100%
Analog input FR (A2)
bias
n061
0%
H3-04
0%
Analog input filter time
constant
n062
0.10
sec
H3-13
0.03
sec
SI-T Watchdog error
operation selection
n063
0
-
-
-
No ML support
Operation at frequency
reference loss selection
n064
0
L4-05
0
V7
V1000
n064
→0
L4-05
→0
n064
→1
L4-05
→1 and
L4-06
→fref value
Analog output AM
Monitor type selection
n065
0
-
-
Use terminal FM for analog and terminal
MP for pulse output signals.
Analog output AM
function selection
n066
0
H4-01
102
V7
V1000
n066
→0
H4-01
→102
n066
→1
H4-01
→103
n066
→2
H4-01
→107
n066
→3
H4-01
→109
n066
→4
H4-01
→108
n066
→5
H4-01
→106
n066
→6
H4-01
→101
Analog output AM gain
n067
1.00
H4-02
100.0%
Analog frequency ref.
gain (Volt. input CN2)
→ Terminal A2 gain
n068
100%
H3-11
100.0%
H3-09 must be set to 0 or 1
Analog freq. reference
bias (Volt. input CN2)
→ Terminal A2 bias
n069
0%
H3-12
0.0%
Analog frequency ref.
filter (Volt. input CN2)
n070
0.10s
H3-13
0.03
Filter time H3-13 is the same for analog
input A1 and A2 in V1000
Analog frequency ref.
gain (Cur. input CN2)
→
Terminal A2 gain
n071
100%
H3-11
100.0%
H3-09 must be set to 2 or 3
Analog frequency ref.
bias (Cur. input CN2)
→
Terminal A2 gain
n072
0%
H3-12
0.0%
Analog frequency ref.
filter (Volt. input CN2)
n073
0.10s
H3-13
0.03
Filter time H3-13 is the same for analog
input A1 and A2 in V1000
Pulse input gain
n074
100%
H6-03
100.0%
Pulse input bias
n075
0%
H6-04
0.0%
Pulse input filter time
n076
0.10 sec
H6-05
0.10 sec
Analog input function
selection (CN2
→
Terminal A2)
n077
0
H3-10
0
V7
V1000
n077
→0
H3-10
→F
n077
→1
H3-10
→2
n077
→2
H3-10
→1
n077
→3
H3-10
→0
n077
→4
H3-10
→4
Drive
Parameter
Function
V7
V1000
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value