Yaskawa VS606 V7 to V1000 User Manual
Page 27

PL.V1000.01 Transition Guide 4/1/09
Page 27 of 38
Yaskawa Electric America, Inc.
Product Transition Guide
PL. V1000.01 Rev: 4/1/09
PID feedback loss
detection level
n137
0%
b5-13
0%
PID feedback loss
detection time
n138
1.0 sec
b5-14
1.0 sec
Auto tuning selection
n139
0
T1-01
0
V7
V1000
n139
→0
b8-01
→0
n139
→1
b8-01
→1
Energy saving
coefficient
n140
b8-04
o2-04
dep.
Value is different to V7 and capacity
dependent
Energy saving voltage
lower limit (60Hz)
n141
50%
-
-
No need to set.
Energy saving voltage
lower limit (6Hz)
n142
12%
-
-
Power average time
n143
1
-
-
Energy saving voltage
search limit
n144
0%
b8-06
0%
Voltage step width at
100% voltage
n145
0.5%
No need to set.
Voltage step width at
50% voltage
n146
0.1%
Pulse input scaling
n149
2500 Hz
H6-02
1440 Hz
Pulse output function
selection
n150
0
H6-06
102
V7
V1000
H6-06
H6-07
n150
→0
102
1440
n150
→1
E1-04
n150
→6
6xE1-04
n150
→12
12xE1-04
n150
→24
24xE1-04
Pulse output scaling
H6-07
1440 Hz
n150
→36
101
36xE1-04
n150
→40
1440
n150
→41
E1-04
n150
→42
6xE1-04
n150
→43
12xE1-04
n150
→44
24xE1-04
n150
→45
36xE1-04
Memobus
communication error
behavior selection
n151
0
H5-04
3
V7
V1000
H5-04
H5-05
n151
→0
1
1
n151
→1
0
(act. Ramp)
2 (C1-09)
Memobus
communication error
detection
H5-05
1
n151
→2
n151
→3
3
n151
→4 No effect
0
Drive node address
n153
0
H5-01
1F
Drive
Parameter
Function
V7
V1000
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value