PL.V1000.01 Transition Guide 4/1/09

Page 29 of 38

Yaskawa Electric America, Inc.

Product Transition Guide

PL. V1000.01 Rev: 4/1/09

Input open phase

detection level

n166

0%

L8-05

o2-09

dep.

The input phase loss detection level and

time can not be set in V1000. The phase

loss detection can be enabled/ disabled

by setting L8-05.

Input open phase

detection time

n167

0.0 sec

Output open phase

detection level

n168

0%

L8-07

o2-09

dep.

The output phase loss detection level and

time can not be set in V1000. The phase

loss detection can be enabled/ disabled

by setting L8-07.

Output open phase

detection time

n169

0.0 sec

Memobus Enter

command selection

n170

0

-

-

V1000 accepts Enter commands at any

time.

Frequency reference bias

upper limit (up/down2)

n171

0.0%

d4-08

0.0%

Frequency reference bias

lower limit (up/down2)

n172

0.0%

d4-09

0.0%

DC braking P-gain

n173

83

No need to set up in V1000

DC braking integral time

n174

25

Low speed carrier

frequency reduction

n175

0

L8-38

0

V7

V1000

n175

→0

L8-38

→0

n175

→1

L8-38

→1

COPY function selection

n176

rdy

o3-01

0

V7

V1000

n176

→rdy

n176

→rEd

o3-01

→1

n176

→CPy

o3-01

→2

n176

→vFy

o3-01

→3

n176

→vA

n176

→Sno

READ prohibit selection

n177

0

o3-02

0

V7

V1000

n177

→0

o3-02

→0

n177

→1

o3-02

→1

Fault History

n178

-

U2/U3-xx

In the V1000 the last fault can be traced
in the U2-xx monitors. The fault history

is displayed in the U3-xx monitors.

Software version

n179

-

U1-25/

26

Drive

Parameter

Function

V7

V1000

Note

Param.

No.

Initial

Value

Set

Value

Param.

No.

Initial

Value

Set

Value