Yaskawa VS606 V7 to V1000 User Manual
Page 29

PL.V1000.01 Transition Guide 4/1/09
Page 29 of 38
Yaskawa Electric America, Inc.
Product Transition Guide
PL. V1000.01 Rev: 4/1/09
Input open phase
detection level
n166
0%
L8-05
o2-09
dep.
The input phase loss detection level and
time can not be set in V1000. The phase
loss detection can be enabled/ disabled
by setting L8-05.
Input open phase
detection time
n167
0.0 sec
Output open phase
detection level
n168
0%
L8-07
o2-09
dep.
The output phase loss detection level and
time can not be set in V1000. The phase
loss detection can be enabled/ disabled
by setting L8-07.
Output open phase
detection time
n169
0.0 sec
Memobus Enter
command selection
n170
0
-
-
V1000 accepts Enter commands at any
time.
Frequency reference bias
upper limit (up/down2)
n171
0.0%
d4-08
0.0%
Frequency reference bias
lower limit (up/down2)
n172
0.0%
d4-09
0.0%
DC braking P-gain
n173
83
–
–
–
No need to set up in V1000
DC braking integral time
n174
25
Low speed carrier
frequency reduction
n175
0
L8-38
0
V7
V1000
n175
→0
L8-38
→0
n175
→1
L8-38
→1
COPY function selection
n176
rdy
o3-01
0
V7
V1000
n176
→rdy
–
n176
→rEd
o3-01
→1
n176
→CPy
o3-01
→2
n176
→vFy
o3-01
→3
n176
→vA
–
n176
→Sno
–
READ prohibit selection
n177
0
o3-02
0
V7
V1000
n177
→0
o3-02
→0
n177
→1
o3-02
→1
Fault History
n178
-
U2/U3-xx
In the V1000 the last fault can be traced
in the U2-xx monitors. The fault history
is displayed in the U3-xx monitors.
Software version
n179
-
U1-25/
26
Drive
Parameter
Function
V7
V1000
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value