beautypg.com

Terminals, Main circuit terminals <1, Control terminals, signal levels – Yaskawa VS606 V7 to V1000 User Manual

Page 7

background image

PL.V1000.01 Transition Guide 4/1/09

Page 7 of 38

Yaskawa Electric America, Inc.

Product Transition Guide

PL. V1000.01 Rev: 4/1/09

1.4 Terminals

Main Circuit Terminals <1>

• As the V7 and V1000 may have different terminals sizes (depending on capacity), the terminals must be carefully

checked before replacement (see Section 1-4). <1>

• The main terminal functionality has not been changed between the V7 and the V1000 drive.

Control Terminals, Signal Levels

• The V7 and V1000 initial settings for terminal function are shown below.
• "—" indicates that an equivalent terminal on the other unit does not exist.

Main Terminals

Note

V7

V1000

R/L1

R/L1

Power supply connection

S/L2

S/L2

T/L3

T/L3

U/T1

U/T1

Drive output

V/T2

V/T2

W/T3

W/T3

B1

B1

Braking resistor or external braking unit connection <1>

B2

B2

Braking resistor connection

+1

+1

DC Choke connection, DC power supply input

+2

+2

DC Choke connection

DC power supply input, external braking unit connection <1>
Ground <1>

Control

Terminals

Function

Signal Level

V7

V1000

V7

V1000

S1

Multi-Function input 1
(1: Run forward 0: Stop) <1>

Photocoupler 24 VDC, 8A

isolation <1>

Photocoupler 24 VDC, 8A <1>

S2

Multi-Function input 2
(1: Run reverse 0: Stop) <1>

S3

Multi-Function input 3
(External fault) <1>

S4

Multi-Function input 4
(Fault reset) <1>

S5

Multi-Function input 5
(Multi-step speed 1) <1>

S6

Multi- Function input 6
(Multi-step speed 2) <1>

S7

Multi-Function input 7
(JOG reference) <1>

SC

Multi-Function input common <1>

RP

Pulse input
(frequency reference)

Frequency range:

1.0~32 kHz <1>

Frequency range:

0.5~32 kHz <1>

FS

+V

Analog input power supply

+12 V (max. current 20 mA)

+10.5 V (max. current 20 mA)